Mon - Fri: 9:00 - 19:00
| System | 42-bar technology with a nozzle pressure of 10 bar |
| Application | Equally effective for fires of class A and B |
| Approvals/standards |
System approvals: VdS, CNPP
System standards:
ISO 14520-1, EN 15004, EN 12094
Software: VdS
Agent: VdS, LPCB, FM-UL, APSAD,
NFPA 2001, ISO 14520-5
Positively tested, rated, and approved by
various international organizations
(Gelsenkirchen Hygiene Institut,
U.S. Environmental Protection Agency, etc.)
|
| Extinguishing agent | 3M™ Novec™ 1230 Fire Protection Fluid |
| Agent characteristics | Liquid at atmospheric pressure, colorless, odorless |
| Environmental regulations |
– Not restricted by F-Gas Regulation – Not part of the Kyoto Protocol |
| GWP (global warming potential) | 1 |
| ALT (atmospheric lifetime) | 3 – 5 days |
| NOAEL (no observable adverse effect level) | 10% |
| ODP (ozone depletion potential) | 0 |
Control Panel w/ LED
01 Loop 252 Points Source 170w UL / FM FC922-UE
Control Panel w/ LED
02 Loops 504 Points Source 170w UL / FM FC924-UE
Control Panel w/ LED 02 Loops 504 Points Source 300w UL / FM FC924-UF
Control Panel w/o LED
01 Loop 252 Points Source 170w UL / FM FC922-US
Control Panel w/o LED 01 Loop 252 Points Source 300w UL / FM FC922-UT
Control Panel w/o LED
02 Loops 504 Points Source 170w UL / FM FC924-US
Control Panel w/ LED 02 Loops 504 Points Source 300w UL / FM FC924-UT
Control Panel w/ Voice Evacuation
1 Loop 252 Points UL / FM FV922
Control Panel w/ Voice Evacuation 01 Loop 252 Points Source 300w UL / FM FC922-UF